Install the AC contactor:
(1) Check whether the technical data of the contactor nameplate and the coil (such as rated voltage, current, operating frequency, etc.) meet the actual use requirements.
(2) Check the appearance of the contactor without mechanical damage; when pushing the movable part of the contactor by hand, the contactor should be flexible and free from jamming; the arc-extinguishing cover should be intact and firmly fixed.
(3) Wipe the anti-rust grease on the pole surface of the iron core or the iron scale stuck on the pole surface with kerosene to avoid the armature being stuck after repeated use, which may not be released after the power is cut off.
(4) Measure the coil resistance and insulation resistance of the contactor, which should meet the requirements.
(5) AC contactors should generally be installed on a vertical plane with an inclination of no more than 5°; if there are vents, the holed side should be placed in a vertical direction to facilitate heat dissipation; Arc space, so as to avoid arcing and burning adjacent appliances.
Float level gauge is a liquid level measuring instrument which works based on the principle of constant buoyancy in buoyancy (Archimedes theorem).In the gravity field, the vertical upward force on the object in the fluid due to the density difference with the surrounding fluid is buoyancy.
In a liquid, an object whose overall density is lower than the liquid density will eventually float on the liquid surface. This object can be called a float. Under constant conditions, the buoyancy of the float is constant (constant buoyancy).
When the float is subjected to an upward force less than its own weight or a downward force less than the weight of the liquid equivalent to its own volume, the characteristic that the float will eventually float on the liquid surface will not be changed.
In the steady state, the buoyancy of the float is constant.
When the position of the liquid surface changes vertically, the vertical position of the float will change synchronously with the position of the liquid surface under the action of constant buoyancy.
The float level gauge is a device that displays the vertical position of the float in the form that people can read directly through various mechanical, electromagnetic, optical and other physical means.
Float Level Gauge,Marine Magnetic Float Level Gauge,Liquid Level Float Gauge,Float Type Level Gauge,Magnetic Float Type Level Transmitter
Taizhou Jiabo Instrument Technology Co., Ltd. , https://www.taizhoujiabo.com