3.6/6kv Power Cables Three Cores Cables to IEC 60502

Model NO.: N2XSEY, N2XSEBY, N2XSEFGBY, N2XSERY
Wire Core Material: Cu or Al
Certification: CCC, CE
Model: N2xsey, N2xseby, N2xseyfgby, N2xsery
Brand: Jl
Rated Voltage: 3.6/6kv
Number of Core: 3
Refer Standard: IEC 60502-2
Trademark: JL
Transport Package: Wooden Drum/Steel Drum
Specification: 1.5-630 Mm2
Origin: Jiangsu, China
HS Code: 8544492100
Model NO.: N2XSEY, N2XSEBY, N2XSEFGBY, N2XSERY
Wire Core Material: Cu or Al
Certification: CCC, CE
Model: N2xsey, N2xseby, N2xseyfgby, N2xsery
Brand: Jl
Rated Voltage: 3.6/6kv
Number of Core: 3
Refer Standard: IEC 60502-2
Trademark: JL
Transport Package: Wooden Drum/Steel Drum
Specification: 1.5-630 Mm2
Origin: Jiangsu, China
HS Code: 8544492100
3.6/6kv Power Cables Three Cores Cables to IEC 60502

Standards

IEC 60502 Part 2

Application
The single core cables are designed for distribution of electrical power with nominal voltage Uo/U ranging from 1.8/3KV to 26/35KV and frequency 50Hz. They are suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switchboards and power stations.

Construction:
Conductors: Aluminium or copper conductors
Conductor Screen: extruded layer of semi-conducting crosslinkable compound
Insulation: XLPE
Insulation Screen: semi-conducting crosslinkable compound
Metallic Screen: copper tape or other metallic screens
Separation Sheath: non-hygroscopic PVC or PP Tape.
Inner Sheath (Bedding) for Armoured Cables: Extruded layer of PVC or PE
Armour: Galvanized steel wire, Galvanized steel tape, Copper Tape, Aluminium wire, Aluminium Tape
Over Sheath: PVC, PE, HDPE, MDPE or LSZH

Technical cable
Operating Temperature: up to 90°C
Short Circuit Temperature( 5 seconds maximum duration ): 250°C
Bending Radius: 12 x OD
Current Rating Conditions:
Ground Temperature:
20°C
Ambient Temperature (air): 30°C
Depth of Soil: 0.8m
Thermal Resistance of Soil: 1.5K•m/W
Insulation Thickness:
Nom. Cross Section Area Insulation Thickness at Nominal Voltage
1.8/3KV 3.6/6KV 6/10KV 8.7/15KV 12/20KV 18/30KV 21/35KV 26/35KV
(Um=3.6KV) (Um=7.2KV) (Um=12KV) (Um=17.5KV) (Um=24KV) (Um=36KV) (Um=42KV) (Um=42KV)
mm2 mm mm mm mm mm mm mm mm
  XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE
10 2 2.5 - - - - - -
16 2 2.5 3.4 - - - - -
25 2 2.5 3.4 4.5 - - - -
35 2 2.5 3.4 4.5 5.5 - - -
50 - 185 2 2.5 3.4 4.5 5.5 8 9.3 10.5
240 2 2.6 3.4 4.5 5.5 8 9.3 10.5
300 2 2.8 3.4 4.5 5.5 8 9.3 10.5
400 2 3 3.4 4.5 5.5 8 9.3 10.5
500 - 1600  2.2-2.8  3.2 3.4 4.5 5.5 8 9.3 10.5

Nominal /Operating /Testing Voltages:
Rated Voltage Uo/U Operating Voltage (Um) Testing Voltage
 (rms)
3.6/6KV 7.2KV 12.5KV  
 
3.6/6KV (Um=7.2KV) Power Cables Three Cores Cables Parameter:
Nom.
Cross-Section Area
Nom.
Insulation Thickness
Copper Tape Thickness Copper Wire Screen Area*  Unarmoured Cables Steel Wire Armoured Cables
Nom.
Sheath Thickness
Approx.
Overall Diameter
Approx.
Weight
Nom.
Bedding Thickness
Armour Wire Size Nom.
Sheath Thickness
Approx.
Overall Diameter
Approx.
Weight
CU AL CU AL
mm2 mm mm mm2 mm mm kg/km mm mm mm mm kg/km
10 2.5 0.1 16 2 30 980 790 1.2 2 2.1 36 2310 2120
16 2.5 0.1 16 2 31 1190 890 1.2 2 2.2 38 2600 2290
25 2.5 0.1 16 2.1 34 1560 1080 1.2 2 2.3 41 3080 2600
35 2.5 0.1 16 2.2 37 1930 1270 1.3 2.5 2.4 45 3950 3280
50 2.5 0.1 16 2.3 40 2370 1480 1.3 2.5 2.5 47 4530 3630
70 2.5 0.1 16 2.4 43 3110 1820 1.4 2.5 2.6 51 5510 4210
95 2.5 0.1 16 2.5 47 4000 2200 1.5 2.5 2.8 55 6660 4860
120 2.5 0.1 16 2.6 50 4820 2550 1.5 2.5 2.9 59 7630 5360
150 2.5 0.1 25 2.8 54 5770 2970 1.6 2.5 3 62 8800 6000
185 2.5 0.1 25 2.9 58 6960 3460 1.6 2.5 3.1 66 10180 6670
240 2.6 0.1 25 3.1 65 8940 4340 1.8 3.15 3.4 75 13480 8870
300 2.8 0.1 25 3.3 70 10980 5190 1.9 3.15 3.6 81 15920 10130
400 3 0.1 35 3.5 79 13820 6440 2 3.5 3.9 90 19980 12590
500 3.2 0.1 35 3.7 87 19100 10755 2.1 3.5 4.1 98 24160 14820
630 3.2 0.1 35 4 95 30470 13150 2.2 3.5 4.4 107 29650 17710

3.6/6KV (Um=7.2KV) Power Cables Three Cores Cables Parameter:
Nom.
Cross-Section
Area
Steel Flat Wire Armoured Cables Double Steel Tape Armoured Cables
Nom.
Bedding Thickness
Armour Wire Size Nom.
Sheath Thickness
Approx.
Overall Diameter
Approx.
Weight
Nom.
Bedding Thickness
No of Steel Tapes x Nom Tape Thickness  Nom.
Sheath Thickness
Approx.
Overall Diameter
Approx.
Weight
CU AL CU AL
mm2 mm mm mm mm kg/km mm mm mm mm kg/km
10 1.2 0.8 1.8 26.9 1415 1235 1.2 2X0.2 1.8 26 1060 885
16 1.2 0.8 1.8 29.2 1725 1445 1.2 2X0.2 1.8 28.3 1340 1055
25 1.2 0.8 1.9 32.2 2165 1735 1.2 2X0.2 1.9 31.3 1735 1305
35 1.3 0.8 2 35 2645 2025 1.3 2X0.2 2 34.1 2170 1555
50 1.3 0.8 2.1 37.4 3075 2295 1.3 2X0.5 2.1 38 2950 2170
70 1.4 0.8 2.2 41 3915 2755 1.4 2X0.5 2.3 41.8 3795 2635
95 1.5 0.8 2.3 45.3 4840 3335 1.5 2X0.5 2.4 46.1 4810 3200
120 1.5 0.8 2.4 48.7 5915 3855 1.5 2X0.5 2.5 49.5 5770 3705
150 1.6 0.8 2.5 52.1 6930 4395 1.6 2X0.5 2.6 52.9 6775 4235
185 1.6 0.8 2.6 56.2 8265 5100 1.6 2X0.5 2.8 57.2 8120 4950
240 1.8 0.8 2.8 62.2 10440 6220 1.8 2X0.5 2.9 63 10250 6025
300 1.9 0.8 3 68.2 12780 7420 1.9 2X0.5 3.1 69 12570 7200
400 2 0.8 3.3 75.9 15970 9110 2 2X0.5 3.4 76.7 15740 8870
500 2.1 0.8 3.5 84.2 19940 11130 2.1 2X0.8 3.6 86.5 20550 11750
630 2.2 0.8 3.7 93.5 25120 13670 2.2 2X0.8 3.9 96 25830 14400


3.6/6KV Power Cables Three Cores Cables to IEC 60502 Electrical Data
Nom. Cross- Section Area D C Resistance
CU / AL
A C Resistance
 CU / AL
Short Circuit Rating of Conductor
CU / AL
(1 sec)
Capaci tance Charging Current Short Circuit Rating of Copper Wire Screen Per Core(1 sec) Short Circuit Rating of Copper Tape Screen Per Core(1 sec) Reactance Inductance
mm² μΩ/m μΩ/m kA pF/m mA/m kA kA μΩ/m μΩ/m
50 387/641 494/822 6.8/4.4 332 0.4 2.6 0.5 102 330
70 268/443 343/568 9.8/6.3 383 0.46 2.6 0.6 97 310
95 193/320 248/410 13.3/8.5 432 0.52 2.6 0.6 92 290
120 153/253 196/325 17.2/11.0 474 0.57 2.6 0.7 89 280
150 124/206 159/265 21.2/13.5 511 0.61 4.3 0.7 87 280
185 99.1/164 128/211 26.6/17.0 562 0.67 4.3 0.8 86 270
240 75.4/125 98/161 34.9/22.3 602 0.72 4.3 0.9 83 260
300 60.1/100 80/130 43.8/28.0 622 0.75 4.3 1 82 260
400 47.0/77.8 64/102 57.3/36.6 648 0.78 5.8 1.1 80 250
500 36.6/60.5 51/81 72.3/46.2 668 0.82 5.8 1.2 78 250
630 28.3/46.9 42/64 91.2/58.3 758 0.92 5.8 1.3 76 240
3.6/6kv Power Cables Three Cores Cables to IEC 60502
3.6/6kv Power Cables Three Cores Cables to IEC 60502

3.6/6kv Power Cables Three Cores Cables to IEC 60502
3.6/6kv Power Cables Three Cores Cables to IEC 60502





3.6/6kv Power Cables Three Cores Cables to IEC 60502




  3.6/6kv Power Cables Three Cores Cables to IEC 60502

Standards

IEC 60502 Part 2

Application
The single core cables are designed for distribution of electrical power with nominal voltage Uo/U ranging from 1.8/3KV to 26/35KV and frequency 50Hz. They are suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switchboards and power stations.

Construction:
Conductors: Aluminium or copper conductors
Conductor Screen: extruded layer of semi-conducting crosslinkable compound
Insulation: XLPE
Insulation Screen: semi-conducting crosslinkable compound
Metallic Screen: copper tape or other metallic screens
Separation Sheath: non-hygroscopic PVC or PP Tape.
Inner Sheath (Bedding) for Armoured Cables: Extruded layer of PVC or PE
Armour: Galvanized steel wire, Galvanized steel tape, Copper Tape, Aluminium wire, Aluminium Tape
Over Sheath: PVC, PE, HDPE, MDPE or LSZH

Technical cable
Operating Temperature: up to 90°C
Short Circuit Temperature( 5 seconds maximum duration ): 250°C
Bending Radius: 12 x OD
Current Rating Conditions:
Ground Temperature:
20°C
Ambient Temperature (air): 30°C
Depth of Soil: 0.8m
Thermal Resistance of Soil: 1.5K•m/W
Insulation Thickness: